Wiring in a metal-roof house ages faster in the heat, and its allowable current must be derated for ambient temperature. The space under the roof sheeting and the roof cavity are the hottest places in the building, so avoid running wiring there. Choose a conductor size and a heat rating that are sufficient under the temperature correction factors of the Regulations for Installation of Customer Electrical Equipment (用戶用電設備裝置規則, "the Installation Rules"). Wiring must be done by a qualified electrician. This article helps homeowners read the specifications and know what to ask. It cannot replace on-site design and installation.
Metal Roof House Wiring: Heat Rating and Ampacity Derating

This article is compiled from publicly available online sources for general reference only; readers should independently verify and judge its accuracy, and it is not legal, tax, medical or engineering advice. Rules, fees and subsidies change; check the latest notice from the responsible authority before acting. For electrical, gas, structural or health risks, consult a qualified professional.
This is the English edition of a Chinese article, adapted with AI assistance and checked against the original. Where the two differ, the Chinese version and the official sources it cites prevail.
What heat does to electric wire
Insulation ages and hardens
The outer insulation of a wire is a plastic-type material. After a long time in high heat and sunlight, it gradually becomes hard and brittle, and cracks may appear on the surface. A metal-roof house is heated by the sun during the day and cools at night, so the material expands and contracts repeatedly, which puts even more strain on the outer sheath. Once the insulation cracks, the protection between the conductor and the metal conduit or sheet metal becomes thinner, and the chance of leakage or a short circuit goes up. Aging speed depends on the material, the temperature, the load current and the installation environment, so no single service life can be applied.
How ambient temperature relates to allowable current
A wire heats up when current flows, and that heat has to be carried away by the surrounding air. The higher the ambient temperature, the less room there is for heat to dissipate, and the less current the same wire can carry safely. The values in an ampacity table are based on a reference ambient temperature. When the environment is hotter than that reference, the value must be multiplied by a correction factor and lowered, or the conductor temperature will exceed the heat limit of the insulation. A closed roof cavity or the space under the roof in summer easily keeps wiring in a higher ambient temperature, so both wire selection and design must take this into account.
How to read wire specifications
Insulation heat rating markings
The outer sheath of a wire is usually printed with the brand, conductor size, voltage rating and insulation temperature rating. The exact marking format depends on the product and the manufacturer's datasheet. Before buying, ask the supplier for the datasheet and confirm the maximum allowable conductor temperature, and do not look only at the conductor size. If the markings are unclear or can no longer be read, treat the rating as unconfirmed and do not use that wire in a hot location.
PVC versus cross-linked PE insulation
| Insulation type | Maximum conductor temperature (typical specification) | Where it applies |
|---|---|---|
| PVC (polyvinyl chloride) | 70°C | Common in ordinary indoor wiring; in hot environments the allowable current must be reduced substantially |
| Cross-linked PE (XLPE) | 90°C | Higher heat resistance, common in cables; can be considered for hot locations |
| Other heat-rated products | As marked on the product | Whether it is suitable is decided by the manufacturer's datasheet and the Installation Rules |
The table above gives general values for typical product specifications. Whether a given model is suitable for a particular location must be decided under the Installation Rules, the CNS wire and cable standards and the manufacturer's datasheet.
How to look up wire size and ampacity tables
The Installation Rules include a conductor ampacity table that lists the allowable current by conductor size, insulation type and installation method (for example in conduit or exposed). When using it, first identify the insulation type of the wire, then look at the installation conditions, and finally apply the corrections for ambient temperature and for the number of wires in a conduit. You can make a first estimate with the site's wire size and breaker calculator, but the formal design still follows the current provisions.
How to use temperature correction factors
The correction tables in the Installation Rules
The ambient temperature correction factors in the rules are listed by insulation heat rating and actual ambient temperature, and the higher the ambient temperature, the smaller the factor. When there are many wires in one conduit, a further reduction factor must be applied. When selecting, first confirm the insulation type of the wire, then look up the table using the highest ambient temperature that could actually occur, not the average air temperature. Copy the values directly from the provisions and tables in the current National Regulations Database, and do not use old tables reposted online.
A calculation example with stated assumptions
The following is an illustration only. Assume that a certain conductor size has a tabulated allowable current of 20 A at the reference ambient temperature, with assumed ambient temperatures of 45°C and 50°C, and that the correction factors are roughly estimated from the heat balance between the conductor temperature limit and the ambient temperature. The 20 A and the ambient temperatures here are assumptions, not measurements, and they are not values from the rules table. For the actual factors, look up the rules table.
| Assumed ambient temperature | PVC 70°C estimated factor | PVC current after correction | XLPE 90°C estimated factor | XLPE current after correction |
|---|---|---|---|---|
| 45°C | About 0.79 | About 15.8 A | About 0.87 | About 17.3 A |
| 50°C | About 0.71 | About 14.1 A | About 0.82 | About 16.3 A |
You can see that the current the same conductor size can carry drops noticeably in a hotter environment. If the breaker is still set at the original 20 A, the wire may be overloaded for long periods. You can first sort out the load current and power consumption with the appliance electricity cost calculator.
Wiring location and conduit
Avoid the space under the roof sheeting and the cavity
After a metal roof is heated by the sun, the air under the roof sheeting and in the cavity builds up heat most easily and also loses heat with difficulty. Wiring routes should preferably go along lower wall positions that are ventilated and cooler, so that wires do not sit close to the roof for long periods or get crowded into the cavity. If a route must pass through such a space, raise the heat rating of the wire, lower the load, and discuss rerouting with a qualified electrician. For independent power supply and meter issues for rooftop-addition households, see the article Rooftop Addition Independent Electricity Meter.
Choosing metal conduit, PVC conduit or trunking in a metal-roof house
Metal conduit has high mechanical strength and must be properly bonded to ground under the rules. PVC conduit resists corrosion and is light, but it may deform under high heat and sunlight, so pay attention to fixing intervals and thermal expansion and contraction. Trunking suits exposed indoor wiring, and the number of wires it holds must still comply with the rules. The number of wires in a conduit also affects the allowable current, so this must be calculated as well. Which type to use should be decided by a qualified electrician based on on-site temperature, current-carrying capacity and maintenance needs.
Add a grommet where wire passes through sheet metal
Where a wire passes through a hole in a sheet metal panel or a metal box, the edge may be sharp, so a grommet or wire protector must be fitted to keep the insulation from being worn through. Small vibrations caused by wind also make the sheath rub against the sheet metal edge again and again, and over a long time it is even more likely to wear through.
Warning signs of aging and when to inspect
When any of the following appears, we recommend having a qualified electrician come and inspect. You can check item by item against Signs for Inspecting Old House Electrical Safety and Old House Electrical Safety Rules Checklist:
- Wire sheath that has hardened, cracked or changed color, or a burning smell
- Sockets, switches or plugs that run warm, or a faceplate that has turned yellow
- A breaker that trips often, or one that trips as soon as the air conditioner or an electric heating device is turned on
- Wires lying directly against the sheet metal, or holes without a grommet
- Loose or rusted conduit joints, or signs of standing water
- A slight tingling feeling when touching a metal casing
Adding high-power equipment, changing an air conditioner, or renovating the roof of a metal-roof house are also good times to check the wiring.
Frequently asked questions
How often should wiring in a metal-roof house be replaced?
There is no uniform official replacement interval to rely on. We suggest judging by warning signs such as appearance, temperature rise and tripping, and having a qualified electrician inspect and assess. For circuits in hot locations, the interval between inspections can be shortened.
Can a wire still be used if its sheath has become hard and brittle?
If the sheath has become hard and brittle or has cracked, the insulation performance has declined and we do not recommend continuing to use it. Have a qualified electrician assess it for replacement, and do not wrap it with tape yourself and keep using it.
Can I use an extension cord for an air conditioner in a metal-roof house?
An air conditioner draws a large current and runs for long hours, so the extension cord's wire size and plug easily overheat, and long-term use is not recommended. An air conditioner should have a dedicated circuit according to the model's specifications, and the details should be installed by a qualified electrician.
Is it acceptable to run wire directly against the sheet metal?
It is not recommended. Sheet metal gets hot after sun exposure, and a wire lying against it faces heat and friction at the same time, so the insulation is easily damaged. If leakage occurs, the whole sheet metal panel could become live. The wire should be run in conduit, fixed in place, and kept at a distance from the roof.